Página 1 - Series FlexSwitch

[]Installation, Operation and MaintenanceNuclear Qualifi ed FLT 93 Series FlexSwitchDoc 06EN003409®TMFlow, Level, Temperature Switch/MonitorModels: F

Página 2

FLT® Series FlexSwitchTM10 Fluid Components International LLC INTENTIONALLY LEFT BLANK

Página 3 - Table of Contents

FLT® Series FlexSwitchTM INSTALLATIONFluid Components International LLC 112 INSTALLATIONReceiving/Inspection• Unpack carefully.• Verify that all i

Página 4

INSTALLATION FLT® Series FlexSwitchTM12 Fluid Components International LLC Verify Sensing Element Flow Direction and Placement Orientation (Level Ap

Página 5

FLT® Series FlexSwitchTM INSTALLATIONFluid Components International LLC 13Packing Gland Assembly1. Threaded or fl anged packing gland mounts are av

Página 6

INSTALLATION FLT® Series FlexSwitchTM14 Fluid Components International LLC Install and Wire the Enclosure(s)Caution: In applications where the sens

Página 7 - 1 GENERAL

FLT® Series FlexSwitchTM INSTALLATIONFluid Components International LLC 15Wiring the Local Enclosure This procedure is for instruments with the con

Página 8 - Technical Speci cation

INSTALLATION FLT® Series FlexSwitchTM16 Fluid Components International LLC relay board is in the same enclosure as the control circuit. Both boards

Página 9

FLT® Series FlexSwitchTM INSTALLATIONFluid Components International LLC 17Wiring Output Signal TerminalsTwo output signals are provided on the cont

Página 10 - INTENTIONALLY LEFT BLANK

INSTALLATION FLT® Series FlexSwitchTM18 Fluid Components International LLC INTENTIONALLY LEFT BLANK

Página 11 - 2 INSTALLATION

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 193 OPERATIONCaution: The control circuit contains electrostatic discharge (E

Página 12 - Install the Sensing Element

FLT® Series FlexSwitchTM Fluid Components International LLC Notice of Proprietary RightsThis document contains confi dential technical data, includ

Página 13

OPERATION FLT® Series FlexSwitchTM20 Fluid Components International LLC Alarm Set Point AdjustmentsNumerical Adjustment Versus Adjustment by Observa

Página 14

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 21JumperJ32 J12 J13 J14 J33FLT93-F ELEMENT WATTAGE(560 OHM HTR)0.57 WATTS0.52

Página 15

OPERATION FLT® Series FlexSwitchTM22 Fluid Components International LLC Figure 3-2 5298 Control Circuit Component LocationsNumerical Alarm Set Poin

Página 16

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 23Detecting Decreasing Flow (low fl ow alarm)1. Stop the process fl ow and allo

Página 17

OPERATION FLT® Series FlexSwitchTM24 Fluid Components International LLC 4. Record this value. Calculated Set Point = ________ volts DCNote: The c

Página 18 - INSTALLATION FLT

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 257. Raise the process fl uid level so the sensing element is wet.8. Allow th

Página 19 - 3 OPERATION

OPERATION FLT® Series FlexSwitchTM26 Fluid Components International LLC Detecting Wet Condition (high level alarm)If the status LED is on, turn the

Página 20 - Alarm Set Point Adjustments

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 27Note: The calculated set point must be at least 0.020 volts greater than th

Página 21

OPERATION FLT® Series FlexSwitchTM28 Fluid Components International LLC Note: The alarm can be set for a specifi c fl ow rate. Follow the Air/Gas Fl

Página 22

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 29Detecting Wet Condition (adjustment with sensing element dry)Caution: Give

Página 23 - FIELD ADJUSTABLE

FLT® Series FlexSwitchTM 06EN003409 Rev. -Fluid Components International LLC 3Table of Contents1 GENERAL ...

Página 24

OPERATION FLT® Series FlexSwitchTM30 Fluid Components International LLC Detecting Increasing Temperature (high temperature alarm)1. Slide the mode s

Página 25

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 31Converting Temp Out Voltage to Temperature in Degrees F or Degrees CThis for

Página 26

OPERATION FLT® Series FlexSwitchTM32 Fluid Components International LLC 0.00385 OHMS/OHMS/ºC 1000 OHM PLATINUM SENSORSTEMPERATURE VERSUS VOLTAGE OUT

Página 27

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 330.00385 OHMS/OHMS/ºC 1000 OHM PLATINUM SENSORSTEMPERATURE VERSUS VOLTAGE OUT

Página 28 - Adjustment by Observation

OPERATION FLT® Series FlexSwitchTM34 Fluid Components International LLC 0.00385 OHMS/OHMS/ºC 1000 OHM PLATINUM SENSORSTEMPERATURE VERSUS VOLTAGE OUT

Página 29

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 350.00385 OHMS/OHMS/ºC 1000 OHM PLATINUM SENSORSTEMPERATURE VERSUS VOLTAGE OUT

Página 30

OPERATION FLT® Series FlexSwitchTM36 Fluid Components International LLC 0.00385 OHMS/OHMS/ºC 1000 OHM PLATINUM SENSORSTEMPERATURE VERSUS VOLTAGE OUT

Página 31

FLT® Series FlexSwitchTM OPERATIONFluid Components International LLC 37 Fail Safe Alarm SettingThese procedures set the second relay to detect com

Página 32

OPERATION FLT® Series FlexSwitchTM38 Fluid Components International LLC Low Level Alarm Settings (Sensing Element Normally Wet)For the low level fa

Página 33

FLT® Series FlexSwitchTM MAINTENANCEFluid Components International LLC 394 MAINTENANCEWarning: To avoid hazards to personnel, ensure that all envi

Página 34

06EN003409 Rev. - FLT® Series FlexSwitchTM4 Fluid Components International LLC Level Applications ...

Página 35

MAINTENANCE FLT® Series FlexSwitchTM40 Fluid Components International LLC INTENTIONALLY LEFT BLANK

Página 36

FLT® Series FlexSwitchTM TROUBLESHOOTINGFluid Components International LLC 415 TROUBLESHOOTINGWarning: Only qualifi ed personnel should attempt to t

Página 37 - Fail Safe Alarm Setting

TROUBLESHOOTING FLT® Series FlexSwitchTM42 Fluid Components International LLC If conditions and specifi cations are satisfactory, then refer to the tr

Página 38 - C00534-2-2

FLT® Series FlexSwitchTM TROUBLESHOOTINGFluid Components International LLC 43Troubleshooting the Flow TransmitterWith power applied measure 9 volts

Página 39 - 4 MAINTENANCE

TROUBLESHOOTING FLT® Series FlexSwitchTM44 Fluid Components International LLC 5 Fuse Check Turn off the power to the FLT and remove the control circu

Página 40 - MAINTENANCE FLT

FLT® Series FlexSwitchTM APPENDIX A - DRAWINGSFluid Components International LLC 45APPENDIX A DRAWINGSPWB Module 5298 - Dual Alarm

Página 41 - 5 TROUBLESHOOTING

APPENDIX A - DRAWINGS FLT® Series FlexSwitchTM46 Fluid Components International LLC INTENTIONALLY LEFT BLANK

Página 42

FLT® Series FlexSwitchTM APPENDIX B - GLOSSARYFluid Components International LLC 47APPENDIX B GLOSSARYAbbreviationsDelta-R (DR) Differential Resis

Página 43

APPENDIX B - GLOSSARY FLT® Series FlexSwitchTM48 Fluid Components International LLC INTENTIONALLY LEFT BLANK

Página 44

FLT® Series FlexSwitchTM APPENDIX C - TEMP COMPFluid Components International LLC 49APPENDIX C TEMPERATURE COMPENSATIONIntroductionTemperature co

Página 45 - APPENDIX A DRAWINGS

FLT® Series FlexSwitchTM 06EN003409 Rev. -Fluid Components International LLC 5APPENDIX A DRAWINGS ...

Página 46 - APPENDIX A - DRAWINGS FLT

APPENDIX C - TEMP COMP FLT® Series FlexSwitchTM50 Fluid Components International LLC 7. Adjust pot R8 (below the yellow LED) until the ohm value fo

Página 47 - APPENDIX B GLOSSARY

FLT® Series FlexSwitchTM APPENDIX C - TEMP COMPFluid Components International LLC 51POWER SUPPLY SETTINGSFLT93-S3 Watts 1.75 Watts 0.75 Watts 0.21

Página 48 - APPENDIX B - GLOSSARY FLT

APPENDIX C - TEMP COMP FLT® Series FlexSwitchTM52 Fluid Components International LLC TEMP COMP R5 R8FACTOR K OHMS K OHMS0.042 119.75 263.160.041 119

Página 49 - Introduction

FLT® Series FlexSwitchTM APPENDIX D - CUSTOMER SERVICEFluid Components International LLC 53APPENDIX D CUSTOMER SERVICECustomer Service/ Technical

Página 50 - Field Temp Comp Calibration

APPENDIX D - CUSTOMER SERVICE FLT® Series FlexSwitchTM54 Fluid Components International LLC Return to Stock EquipmentThe customer is responsible for

Página 51

FLT® Series FlexSwitchTM APPENDIX D - CUSTOMER SERVICEFluid Components International LLC 551. Return Customer Information Returning Company’s Nam

Página 52

APPENDIX D - CUSTOMER SERVICE FLT® Series FlexSwitchTM56 Fluid Components International LLC The following Return Authorization Request form and Deco

Página 53 - APPENDIX D CUSTOMER SERVICE

FLT® Series FlexSwitchTM APPENDIX D - CUSTOMER SERVICEFluid Components International LLC 57WARRANTIESGoods furnished by the Seller are to be within

Página 54

Fluid Components International LLC 06EN003409 Rev. - FCI’s Complete Customer Commitment. WorldwideISO 9001 and AS9100 Certifi edNotice of Proprietary

Página 55 - RA #______________

FLT® Series FlexSwitchTM6 Fluid Components International LLC INTENTIONALLY LEFT BLANK

Página 56

FLT® Series FlexSwitchTM GENERALFluid Components International LLC 71 GENERALDescriptionThe FLT Series models are multipurpose measurement instrum

Página 57 - WARRANTIES

TECHNICAL SPECIFICATIONS FLT® Series FlexSwitchTM8 Fluid Components International LLC ApplicationFlow rate and /or level /interface and temperature

Página 58 - ISO 9001 and AS9100 Certifi ed

FLT® Series FlexSwitchTM TECHNICAL SPECIFICATIONSFluid Components International LLC 9  Factory Calibrated Switch Point AccuracyAny fl ow rate within